Friction Loss Factors

Some examples of the Friction Loss Factor values, for piping circuits (may be added for several singularities):

45° elbow, standard 0.35
90° elbow, standard 0.75
90° elbow, long radius 0.45
Tee, along run, branch inactive 0.4
Tee, used as elbow 1.5
Gate valve, open 0.17
Gate valve, ¾ open 0.9
Gate valve, ½ open 4.5
Gate valve, ¼ open 24
Diaphragm valve, open 2.3
Diaphragm valve, ¾ open 2.6
Diaphragm valve, ½ open 4.3
Diaphragm valve, ¼ open 21
Butterfly valve, 5° 0.24
Butterfly valve, 20° 1.54
Butterfly valve, 40° 10.8
Butterfly valve, 60° 11.8
Non-return valve, disk 10
Non-return valve, ball 70
Water meter, disk 7.0
Water meter, piston 15
Water meter, Turbine 6.0